2 楼
Clean the flame sensor with a steel wool carefully, clean the ground wire
connected with the metal frame as well and secure the screw tightly.
connected with the metal frame as well and secure the screw tightly.
s*g
5 楼
Thanks for the clarification.
The story happened two years ago. First I suspect
it is the flame sensor. Then found a burned relay
on the control board. After replacing the relay, it
works just fine.
.
【在 d**j 的大作中提到】![](/moin_static193/solenoid/img/up.png)
:
: Supposed the relay is burned, your blower can't start after the burner
: lights, and the burner should shut down by an opening of high limited
: control. There is a different story, your control board should be replaced.
The story happened two years ago. First I suspect
it is the flame sensor. Then found a burned relay
on the control board. After replacing the relay, it
works just fine.
.
【在 d**j 的大作中提到】
![](/moin_static193/solenoid/img/up.png)
:
: Supposed the relay is burned, your blower can't start after the burner
: lights, and the burner should shut down by an opening of high limited
: control. There is a different story, your control board should be replaced.
d*j
7 楼
Use small size drill bits to clean the burner orifice if the above can't
solve the problem, after that, should check the gas pressure and do a
continuity test at the
solenoid valve.
【在 d**j 的大作中提到】
![](/moin_static193/solenoid/img/up.png)
: Clean the flame sensor with a steel wool carefully, clean the ground wire
: connected with the metal frame as well and secure the screw tightly.