s*w
2 楼
一个半月前曾经在板上请教过大家furnace的问题.
情况是,家里的furnace,开了之后,大概run 30分钟,就会自动熄火。于是我们需要
手动去restart furnace (关了再开)。家里thermostat设置70F,怎么都不会达到这
个setpoint,除非我们自己不停的手动restart
当初有位大侠说,可能是filter的问题。于是1个月前我们把filter拿走或者换了big
hole的filter,furnace就一直没有问题,运作良好。
这一个半月中间,home warranty派来的contract把control board给换了
可是自从这周开始,furnace老毛病又犯了
这次问题更加严重,不管是不是用filter,furnace都会自动shut down。
仔细看了一下,启动后,先是blow热气;然后中间有一段时间blow 冷气,查看了error
code,是3 flash red - Pressure Switch stuck open;接着再blow热气一段时间;
最后就熄火,报错的信号灯是6 flash red - Pressure switch cycle lockout
然后furnace再也不会自己启动,直到我们把它关了再开
之前一直以为是filter的问题,看来我错了
请教板上的大侠,这个到底是什么问题呢?该如何解决?
home warranty下周还会派人来,但是我觉得那些人不太可靠。所以想先听听板上高手
的意见
万分感谢
情况是,家里的furnace,开了之后,大概run 30分钟,就会自动熄火。于是我们需要
手动去restart furnace (关了再开)。家里thermostat设置70F,怎么都不会达到这
个setpoint,除非我们自己不停的手动restart
当初有位大侠说,可能是filter的问题。于是1个月前我们把filter拿走或者换了big
hole的filter,furnace就一直没有问题,运作良好。
这一个半月中间,home warranty派来的contract把control board给换了
可是自从这周开始,furnace老毛病又犯了
这次问题更加严重,不管是不是用filter,furnace都会自动shut down。
仔细看了一下,启动后,先是blow热气;然后中间有一段时间blow 冷气,查看了error
code,是3 flash red - Pressure Switch stuck open;接着再blow热气一段时间;
最后就熄火,报错的信号灯是6 flash red - Pressure switch cycle lockout
然后furnace再也不会自己启动,直到我们把它关了再开
之前一直以为是filter的问题,看来我错了
请教板上的大侠,这个到底是什么问题呢?该如何解决?
home warranty下周还会派人来,但是我觉得那些人不太可靠。所以想先听听板上高手
的意见
万分感谢
s*w
4 楼
晕,竟然上首页了,但是都没有人回复///
error
【在 s********w 的大作中提到】
: 一个半月前曾经在板上请教过大家furnace的问题.
: 情况是,家里的furnace,开了之后,大概run 30分钟,就会自动熄火。于是我们需要
: 手动去restart furnace (关了再开)。家里thermostat设置70F,怎么都不会达到这
: 个setpoint,除非我们自己不停的手动restart
: 当初有位大侠说,可能是filter的问题。于是1个月前我们把filter拿走或者换了big
: hole的filter,furnace就一直没有问题,运作良好。
: 这一个半月中间,home warranty派来的contract把control board给换了
: 可是自从这周开始,furnace老毛病又犯了
: 这次问题更加严重,不管是不是用filter,furnace都会自动shut down。
: 仔细看了一下,启动后,先是blow热气;然后中间有一段时间blow 冷气,查看了error
error
【在 s********w 的大作中提到】
: 一个半月前曾经在板上请教过大家furnace的问题.
: 情况是,家里的furnace,开了之后,大概run 30分钟,就会自动熄火。于是我们需要
: 手动去restart furnace (关了再开)。家里thermostat设置70F,怎么都不会达到这
: 个setpoint,除非我们自己不停的手动restart
: 当初有位大侠说,可能是filter的问题。于是1个月前我们把filter拿走或者换了big
: hole的filter,furnace就一直没有问题,运作良好。
: 这一个半月中间,home warranty派来的contract把control board给换了
: 可是自从这周开始,furnace老毛病又犯了
: 这次问题更加严重,不管是不是用filter,furnace都会自动shut down。
: 仔细看了一下,启动后,先是blow热气;然后中间有一段时间blow 冷气,查看了error
r*u
5 楼
我碰到过。换pressure limit switch再换thermostat
error
【在 s********w 的大作中提到】
: 一个半月前曾经在板上请教过大家furnace的问题.
: 情况是,家里的furnace,开了之后,大概run 30分钟,就会自动熄火。于是我们需要
: 手动去restart furnace (关了再开)。家里thermostat设置70F,怎么都不会达到这
: 个setpoint,除非我们自己不停的手动restart
: 当初有位大侠说,可能是filter的问题。于是1个月前我们把filter拿走或者换了big
: hole的filter,furnace就一直没有问题,运作良好。
: 这一个半月中间,home warranty派来的contract把control board给换了
: 可是自从这周开始,furnace老毛病又犯了
: 这次问题更加严重,不管是不是用filter,furnace都会自动shut down。
: 仔细看了一下,启动后,先是blow热气;然后中间有一段时间blow 冷气,查看了error
error
【在 s********w 的大作中提到】
: 一个半月前曾经在板上请教过大家furnace的问题.
: 情况是,家里的furnace,开了之后,大概run 30分钟,就会自动熄火。于是我们需要
: 手动去restart furnace (关了再开)。家里thermostat设置70F,怎么都不会达到这
: 个setpoint,除非我们自己不停的手动restart
: 当初有位大侠说,可能是filter的问题。于是1个月前我们把filter拿走或者换了big
: hole的filter,furnace就一直没有问题,运作良好。
: 这一个半月中间,home warranty派来的contract把control board给换了
: 可是自从这周开始,furnace老毛病又犯了
: 这次问题更加严重,不管是不是用filter,furnace都会自动shut down。
: 仔细看了一下,启动后,先是blow热气;然后中间有一段时间blow 冷气,查看了error
m*9
6 楼
If pressure switch is open, it means the venting system does not work
properly. Without venting, combustion byproducts will stay inside house.
Inducer failure or vent pipe clog and other things could cause pressure
switch open. furnace will shut down if pressure switch is open,it is a kind
of safety feature.
Pressure switch can fail too. But should assume pressure switch does it's
job and make sure vent Works fine.
properly. Without venting, combustion byproducts will stay inside house.
Inducer failure or vent pipe clog and other things could cause pressure
switch open. furnace will shut down if pressure switch is open,it is a kind
of safety feature.
Pressure switch can fail too. But should assume pressure switch does it's
job and make sure vent Works fine.
e*y
7 楼
很可能是capacitor旧了,换个新的capacitor应该可以解决问题。如果还不行,那就是
control board,换control board
kind
【在 m******9 的大作中提到】
: If pressure switch is open, it means the venting system does not work
: properly. Without venting, combustion byproducts will stay inside house.
: Inducer failure or vent pipe clog and other things could cause pressure
: switch open. furnace will shut down if pressure switch is open,it is a kind
: of safety feature.
: Pressure switch can fail too. But should assume pressure switch does it's
: job and make sure vent Works fine.
control board,换control board
kind
【在 m******9 的大作中提到】
: If pressure switch is open, it means the venting system does not work
: properly. Without venting, combustion byproducts will stay inside house.
: Inducer failure or vent pipe clog and other things could cause pressure
: switch open. furnace will shut down if pressure switch is open,it is a kind
: of safety feature.
: Pressure switch can fail too. But should assume pressure switch does it's
: job and make sure vent Works fine.
m*9
10 楼
That cap is the run cap for indoor blower. Indoor blower failure should not
trigger pressure switch open.if you are sure vent pipe is clean, you can
bypass pressure switch (short out) and check if Inducer (vent motor)stay
running. Sounds like Inducer stop run when get warmed up.either Inducer or
pressure switch is the culprit.
Don't force unit run without venting, toxic carbon monoxide may accumulate
inside house.
trigger pressure switch open.if you are sure vent pipe is clean, you can
bypass pressure switch (short out) and check if Inducer (vent motor)stay
running. Sounds like Inducer stop run when get warmed up.either Inducer or
pressure switch is the culprit.
Don't force unit run without venting, toxic carbon monoxide may accumulate
inside house.
w*m
14 楼
关掉应该是漏气吧,是不是VENT有问题?
l*b
15 楼
楼主你好,后来问题解决了吗?
我这里也有类似问题了,自动熄火,然后下面绿灯闪三下,过一阵又自己点着火了,但
马上就又灭了,屋里温度上不来,好像听到设备有挺大的流水声音。
这是怎么回事那?
多谢谁能给看看。
我这里也有类似问题了,自动熄火,然后下面绿灯闪三下,过一阵又自己点着火了,但
马上就又灭了,屋里温度上不来,好像听到设备有挺大的流水声音。
这是怎么回事那?
多谢谁能给看看。
l*b
17 楼
多谢imore 这么快就答复啦
牌子是heil,具体型号不知道在哪里看呀
看手册上说闪三下,flash 3 = low pressure swith open when should be closed....
什么意思呢?
目前状况是点火以后有时候烧一分钟,有时候烧3分钟就自动熄灭了,就这么反复自动
启动烧起来然后自动熄灭,一个小时也上升不了一度。
有时候突然灭了,就听见一个连着天花板的管子里有哗哗的水声,和这个有关吗?
多谢imore再给看看啊
牌子是heil,具体型号不知道在哪里看呀
看手册上说闪三下,flash 3 = low pressure swith open when should be closed....
什么意思呢?
目前状况是点火以后有时候烧一分钟,有时候烧3分钟就自动熄灭了,就这么反复自动
启动烧起来然后自动熄灭,一个小时也上升不了一度。
有时候突然灭了,就听见一个连着天花板的管子里有哗哗的水声,和这个有关吗?
多谢imore再给看看啊
i*e
19 楼
如果你的事高效率暖气炉(PVC 排气), 你先把furnace condensate trap 拆下来用温
水清洗一下,所有的排水软管都想办法通一下,如果排水是靠水泵打出去的, 确认打
出去的排水管是否畅通。
小排气马达周围的小橡皮管也拔出来吹一下。
贴点图上来
...
【在 l*****b 的大作中提到】
: 多谢imore 这么快就答复啦
: 牌子是heil,具体型号不知道在哪里看呀
: 看手册上说闪三下,flash 3 = low pressure swith open when should be closed....
: 什么意思呢?
: 目前状况是点火以后有时候烧一分钟,有时候烧3分钟就自动熄灭了,就这么反复自动
: 启动烧起来然后自动熄灭,一个小时也上升不了一度。
: 有时候突然灭了,就听见一个连着天花板的管子里有哗哗的水声,和这个有关吗?
: 多谢imore再给看看啊
水清洗一下,所有的排水软管都想办法通一下,如果排水是靠水泵打出去的, 确认打
出去的排水管是否畅通。
小排气马达周围的小橡皮管也拔出来吹一下。
贴点图上来
...
【在 l*****b 的大作中提到】
: 多谢imore 这么快就答复啦
: 牌子是heil,具体型号不知道在哪里看呀
: 看手册上说闪三下,flash 3 = low pressure swith open when should be closed....
: 什么意思呢?
: 目前状况是点火以后有时候烧一分钟,有时候烧3分钟就自动熄灭了,就这么反复自动
: 启动烧起来然后自动熄灭,一个小时也上升不了一度。
: 有时候突然灭了,就听见一个连着天花板的管子里有哗哗的水声,和这个有关吗?
: 多谢imore再给看看啊
s*w
20 楼
今天home warraty来电话说,我的furnace很老,2004年的,买heat exchanger太贵了。
所以就判定是修不好,直接帮我们重新买个新的安装
但是里面有一些费用不在home warranty cover的范围里面
第一个是gas line 大概$200
第二个是 vent piping 大概 $300
最后总共$500左右需要自己出.但是也还算是一个好消息。
所以也没有什么有用的信息可以提供。再次感谢各位给以的意见
现在就希望他们早点派人来安装新的furnace
每天晚上睡前把暖气 调到72度,早上醒来就只有62-63度,冷死了
【在 s********w 的大作中提到】
: 我的要等到heat exchanger买来了才知道是否真的修好
: 这个part,估计至少等2-3周,home warranty才给买了寄到
: 我这个part换了之后,会告诉大家结果如何
所以就判定是修不好,直接帮我们重新买个新的安装
但是里面有一些费用不在home warranty cover的范围里面
第一个是gas line 大概$200
第二个是 vent piping 大概 $300
最后总共$500左右需要自己出.但是也还算是一个好消息。
所以也没有什么有用的信息可以提供。再次感谢各位给以的意见
现在就希望他们早点派人来安装新的furnace
每天晚上睡前把暖气 调到72度,早上醒来就只有62-63度,冷死了
【在 s********w 的大作中提到】
: 我的要等到heat exchanger买来了才知道是否真的修好
: 这个part,估计至少等2-3周,home warranty才给买了寄到
: 我这个part换了之后,会告诉大家结果如何
l*b
21 楼
上来特此感谢 imore ,真不愧是专家诶。
把排水的地方都清理了一下,果然是有一地方堵了,清理以后暖气终于恢复正常工作了
。
把排水的地方都清理了一下,果然是有一地方堵了,清理以后暖气终于恢复正常工作了
。
l*b
22 楼
楼主看看是不是也是什么排水管堵了。因为你的症状和我的一样,温度上不去,烧一会
自动灭,3 flash
自动灭,3 flash
相关阅读
从技术上讲,有没有可能生产馒头机?慎吃猪蹄猪肘之类的,有PP有真相! (转载)这个油烟机怎么样?这个皮影戏节目不错请教白蚁的问题最近有没有Miter Saw的Deal?邮箱撞烂了我为什么不买condo (转载)换了炉子煤气费大将卫生间镜子坏了夫妇俩地,一方买房申请贷款,不行吗?thermastat经常自己reset怎么回事如何便宜寄包裹到中国?春晚看了一半,最憨厚的就两个人是有包子: 求推荐patio用的煤气炉!!!送包子包子包子!买房遇到神经病了说到修插座。。。大家新年好!家里的衣橱里发现了白蚁痕迹,找人过来检查,可检查的人却不上attic看看,正常么?丁丁,你要的hammer drill有deal了 $72.25 from $350