help! Gas furnace has flame but no heat# Living
z*8
1
I tried but could not figure this one out: this gas furnace has flame but no
heat, how is this possible?
I see flame (this means a lot of parts are working) and blower works, but
the air is not warm air.
York package unit (furnace and AC combined)
model no: D1NA030N036606C
year 1999
gas furnace.
Thank you very much in advance for your answer.
avatar
y*j
2
火苗是稳定的蓝色火焰吗?
如果是,那么可能是heat exchanger shut off, 有可能是filter太脏了,或者太密了
, 或者控制阀门,过载温度计坏了。

:I tried but could not figure this one out: this gas furnace has flame but
no heat, how is this possible?
:I see flame (this means a lot of parts are working) and blower works, but
:the air is not warm air.
:York package unit (furnace and AC combined)
:model no: D1NA030N036606C
:year 1999
:gas furnace.
:Thank you very much in advance for your answer.

【在 z*****8 的大作中提到】
: I tried but could not figure this one out: this gas furnace has flame but no
: heat, how is this possible?
: I see flame (this means a lot of parts are working) and blower works, but
: the air is not warm air.
: York package unit (furnace and AC combined)
: model no: D1NA030N036606C
: year 1999
: gas furnace.
: Thank you very much in advance for your answer.

avatar
h*e
3
难得见老张求助,不懂帮顶
avatar
b*y
4
秘鲁有filter? 俺没见过

but
but

【在 y*j 的大作中提到】
: 火苗是稳定的蓝色火焰吗?
: 如果是,那么可能是heat exchanger shut off, 有可能是filter太脏了,或者太密了
: , 或者控制阀门,过载温度计坏了。
:
: :I tried but could not figure this one out: this gas furnace has flame but
: no heat, how is this possible?
: :I see flame (this means a lot of parts are working) and blower works, but
: :the air is not warm air.
: :York package unit (furnace and AC combined)
: :model no: D1NA030N036606C

avatar
y*j
5
他说的是暖气,不是 fireplace.

:秘鲁有filter? 俺没见过

【在 b**********y 的大作中提到】
: 秘鲁有filter? 俺没见过
:
: but
: but

avatar
z*8
6
多谢回答。没搞过HVAC,还请多帮忙。 不知电工接的thermostat 对不对,this unit
has 4 terminal for wire, but he uses 4 wires to connect the 24v thermostat
C=not connected
G=connects to green
Y=connects to black (this could be the furnace)
W=white
R=red
I did more experiments:
1. turn thermostat from off to heat: blower start immediately, but no heat
2. turn thermostat from heat to off: blower stops after a few seconds delay,
but during the few seconds, I swear it is warm air.
attached are some images, I label them A,B,C,D,...,G,H so that we can refer
them to discuss.
Thanks

but
but

【在 y*j 的大作中提到】
: 火苗是稳定的蓝色火焰吗?
: 如果是,那么可能是heat exchanger shut off, 有可能是filter太脏了,或者太密了
: , 或者控制阀门,过载温度计坏了。
:
: :I tried but could not figure this one out: this gas furnace has flame but
: no heat, how is this possible?
: :I see flame (this means a lot of parts are working) and blower works, but
: :the air is not warm air.
: :York package unit (furnace and AC combined)
: :model no: D1NA030N036606C

avatar
z*8
7

unit
delay,

【在 z*****8 的大作中提到】
: 多谢回答。没搞过HVAC,还请多帮忙。 不知电工接的thermostat 对不对,this unit
: has 4 terminal for wire, but he uses 4 wires to connect the 24v thermostat
: C=not connected
: G=connects to green
: Y=connects to black (this could be the furnace)
: W=white
: R=red
: I did more experiments:
: 1. turn thermostat from off to heat: blower start immediately, but no heat
: 2. turn thermostat from heat to off: blower stops after a few seconds delay,

avatar
z*8
8


【在 z*****8 的大作中提到】
:
: unit
: delay,

avatar
r*a
9
摸摸看blower里面的水管热吗?可能circular pump 坏了。

【在 z*****8 的大作中提到】

avatar
z*8
10
where is the "blower里面的水管", I a big fan from outside, and then there is
this G labeled in my image. Where the big fan is, I see two tube connecting
to panel, one is "H", the other is "L", see attached, what are these?

摸摸看blower里面的水管热吗?可能circular pump 坏了。

【在 r********a 的大作中提到】
: 摸摸看blower里面的水管热吗?可能circular pump 坏了。
avatar
r*a
11
blower 的原理就是把热水管的热吹出去。你摸摸furnace 旁边pump 上面那段水管热不
热。

is
connecting

【在 z*****8 的大作中提到】
: where is the "blower里面的水管", I a big fan from outside, and then there is
: this G labeled in my image. Where the big fan is, I see two tube connecting
: to panel, one is "H", the other is "L", see attached, what are these?
:
: 摸摸看blower里面的水管热吗?可能circular pump 坏了。

avatar
r*a
12
忘了问是heat exchanger发热还是热水管?

【在 r********a 的大作中提到】
: blower 的原理就是把热水管的热吹出去。你摸摸furnace 旁边pump 上面那段水管热不
: 热。
:
: is
: connecting

avatar
z*8
13
here is the video
this small fan blow hot

【在 r********a 的大作中提到】
: 忘了问是heat exchanger发热还是热水管?
avatar
i*e
14
第12秒
avatar
z*8
15
yes, this small fan (circulation blower?) push hot exhaust air out. I assume
this is some kind of safety mechanism. I assume as soon as this fan stops,
then the hot air would come out. How to make this fan stop?
Many thanks.

【在 i***e 的大作中提到】
: 第12秒
avatar
i*e
16
9-12秒之间
貌似空调压缩机在同时运行
avatar
z*8
17
有没有什么可以check的,进一步看看是什么问题? 谢了。
avatar
i*e
18
可以的
IMG_20161222_093359.jpg 重新贴图上来,下面接线照清楚点。
avatar
z*8
19
how can you tell if "空调压缩机在同时运行"?
把 Y terminal disconnect to see if the AC can be off?

【在 i***e 的大作中提到】
: 9-12秒之间
: 貌似空调压缩机在同时运行

avatar
z*8
20


【在 i***e 的大作中提到】
: 可以的
: IMG_20161222_093359.jpg 重新贴图上来,下面接线照清楚点。

avatar
i*e
21
by looking at condenser fan
you can try, but it won't help.
check power contactor

【在 z*****8 的大作中提到】
: how can you tell if "空调压缩机在同时运行"?
: 把 Y terminal disconnect to see if the AC can be off?

avatar
z*8
22
OK, I will check the contactor tomorrow if it does not rain too hard.
I expect there is no 24V low volt power to the coil, but the contactor
somehow has shorted the contacts (closed the switch) providing power to the
AC. Is this your diagnosis strategy? This would be a good thing to check,
thank you very much.

【在 i***e 的大作中提到】
: by looking at condenser fan
: you can try, but it won't help.
: check power contactor

avatar
z*8
24
tested the power contactor today. There was 24V on the contactor. Since now
I have
the circuit diagram, I spent some time tracing the circuit, I found the
electrician made two mistakes connecting the thermostats. The first mistake
was the Y and W wires at the thermostats were shorted (the control wires are
stranded type, he did not do a clean job), the second mistake was he
swapped Y and W. This would explain why I can see flame and the contactor is
turned on.
Now the heat is working!!!
Thanks imore for the suggestion.

【在 z*****8 的大作中提到】
: googled and found a manual (I think it matches closely to this unit) here:
: http://pdfstream.manualsonline.com/a/a2ffbb90-5900-48bd-974c-2d6f596dd4da.pdf

avatar
z*8
25
这电工是有license, 也不便宜。气杀我也。我一般不骂人,这次在脑子里默默的!@#
¥%^&* 他一下
avatar
y*j
26
这位电工是色盲吗?

:tested the power contactor today. There was 24V on the contactor. Since
now I have
:the circuit diagram, I spent some time tracing the circuit, I found the
:electrician made two mistakes connecting the thermostats. The first
mistake was the Y and W wires at the thermostats were shorted (the control
wires are stranded type, he did not do a clean job), the second mistake was
he
:swapped Y and W. This would explain why I can see flame and the contactor
is turned on.
:Now the heat is working!!!
:Thanks imore for the suggestion.

【在 z*****8 的大作中提到】
: 这电工是有license, 也不便宜。气杀我也。我一般不骂人,这次在脑子里默默的!@#
: ¥%^&* 他一下