3个月前换了新的Igniter, 今天Igniter一直亮着不打火,维修的人来随便开了一下就
说Heat pipe已经开始生锈和crack, 并且导致main board损坏(没有拿仪器测试),所
以igniter一直亮着,修不了,只能换新的furnace了。这个维修人员开起来没有什么经
验,不知道他的说法对不对?我看网上有人说是temp switch和wire problem也会让
igniter一直亮着。
Furnace和AC都是25年左右,AC工作的很好。如果换的话,哪些是比较中档的牌子,因
为可能几年之内会搬家,不想换最好的。
谢谢
说Heat pipe已经开始生锈和crack, 并且导致main board损坏(没有拿仪器测试),所
以igniter一直亮着,修不了,只能换新的furnace了。这个维修人员开起来没有什么经
验,不知道他的说法对不对?我看网上有人说是temp switch和wire problem也会让
igniter一直亮着。
Furnace和AC都是25年左右,AC工作的很好。如果换的话,哪些是比较中档的牌子,因
为可能几年之内会搬家,不想换最好的。
谢谢
d*j
4 楼
The reason caused your issue could be a sticking relay, a faulty circuit
board or a faulty gas valve, it should not be linked with the heat exchanger
, a cracked heat exchanger can trigger the high limit switch trap and causes
the system shut down, so the tech is lying or without any experience.
The cost to replace a gas valve or a circuit board is around a few hundred
dollars if you can DIY.
If you want to replace a new system, I suggest Ruud or Rheem with 80% Afue
Gas System, they are reliable.
https://www.theacoutlet.com/ra1648aj1na-rcf4821stamca-r801ta100521msa-4-ton
-16-seer-rheem-ruud-100-000-btu-80-afue-gas-system.html?gclid=
CjwKCAjwvuzkBRAhEiwA9E3FUpzqZUYglHFn2Ncaf49wfbDMj6i5VLqJoKtPpb365Nbz09uMdQdm
CRoCivMQAvD_BwE
board or a faulty gas valve, it should not be linked with the heat exchanger
, a cracked heat exchanger can trigger the high limit switch trap and causes
the system shut down, so the tech is lying or without any experience.
The cost to replace a gas valve or a circuit board is around a few hundred
dollars if you can DIY.
If you want to replace a new system, I suggest Ruud or Rheem with 80% Afue
Gas System, they are reliable.
https://www.theacoutlet.com/ra1648aj1na-rcf4821stamca-r801ta100521msa-4-ton
-16-seer-rheem-ruud-100-000-btu-80-afue-gas-system.html?gclid=
CjwKCAjwvuzkBRAhEiwA9E3FUpzqZUYglHFn2Ncaf49wfbDMj6i5VLqJoKtPpb365Nbz09uMdQdm
CRoCivMQAvD_BwE
c*0
6 楼
谢谢大神回复
再请教一下,我家是地下室350sq ft, 一楼800,二楼也是800,one-zone, 这样的话4
ton会不会太大
exchanger
causes
ton
【在 d**j 的大作中提到】
: The reason caused your issue could be a sticking relay, a faulty circuit
: board or a faulty gas valve, it should not be linked with the heat exchanger
: , a cracked heat exchanger can trigger the high limit switch trap and causes
: the system shut down, so the tech is lying or without any experience.
: The cost to replace a gas valve or a circuit board is around a few hundred
: dollars if you can DIY.
: If you want to replace a new system, I suggest Ruud or Rheem with 80% Afue
: Gas System, they are reliable.
: https://www.theacoutlet.com/ra1648aj1na-rcf4821stamca-r801ta100521msa-4-ton
: -16-seer-rheem-ruud-100-000-btu-80-afue-gas-system.html?gclid=
再请教一下,我家是地下室350sq ft, 一楼800,二楼也是800,one-zone, 这样的话4
ton会不会太大
exchanger
causes
ton
【在 d**j 的大作中提到】
: The reason caused your issue could be a sticking relay, a faulty circuit
: board or a faulty gas valve, it should not be linked with the heat exchanger
: , a cracked heat exchanger can trigger the high limit switch trap and causes
: the system shut down, so the tech is lying or without any experience.
: The cost to replace a gas valve or a circuit board is around a few hundred
: dollars if you can DIY.
: If you want to replace a new system, I suggest Ruud or Rheem with 80% Afue
: Gas System, they are reliable.
: https://www.theacoutlet.com/ra1648aj1na-rcf4821stamca-r801ta100521msa-4-ton
: -16-seer-rheem-ruud-100-000-btu-80-afue-gas-system.html?gclid=
相关阅读
加州买房子,房屋检查不满意,应该可以退出吧?肉锅的困惑: 女友送了一张 one-way air ticket..imore请帮忙看一下求一个pier 1的coupon中式装修选购罗汉床的方法(转载)大家都用哪个公司的有线电视服务需要从国内买窗帘吗?Morgage Prequalify的Hardpull是正常的吗?水公司暖气管响有办法修么?无聊弄了一个meter测了一下TDS (转载)求推荐SAN JOSE 附近的PPO产科医生一楼与二楼之间的地板中间有老鼠?木制或者竹子的菜板怎么放不发霉?重做车库地面要多少钱?房子下面挖出了泉水房屋improvement部分租私人房子的注意事项新手问题亲戚的孩子要来玩,申请美国签证时用的委托书要写谁带过来吗? (转载)